Procedure For Commissioning The S7-1500 Automation System - Siemens SIMATIC S7-1500/ET 200MP System Manual

Hide thumbs Also See for SIMATIC S7-1500/ET 200MP:
Table of Contents

Advertisement

System power supply or load current supply
• Are all system power supplies and load current supplies switched off?
• Is the power cable connector correctly wired?
• Has the connection to line voltage been made?
12.3

Procedure for commissioning the S7-1500 automation system

Requirements
• The CPU is in the "Factory settings" state or has been reset to factory settings. You can find
more information in the section Resetting the CPU to factory settings (Page 319).
• The SIMATIC memory card is as delivered or has been formatted.
Commissioning procedure
For the first commissioning of an S7-1500 automation system, we recommend the following
procedure:
Table 12- 1
Procedure for commissioning the SIMATIC S7-1500
Step
Procedure
1
Configure hardware in STEP 7 and perform power balance calcu-
lation (see also "Requirements: CPU as bus device")
2
Create user program
3
Insert required modules
4
Wiring and checking the assembly (system power supplies, front
connectors, etc.)
5
Insert SIMATIC memory card in the CPU
6
Switch on the CPU and system power supply
7
Check LEDs
8
Evaluate information on the CPU's display
9
Load hardware configuration and user program to the CPU
10
Test inputs and outputs
Automation system
System Manual, 01/2023, A5E03461182-AK
12.3 Procedure for commissioning the S7-1500 automation system
Commissioning
See...
Section Power balance calculation
(Page 121)
STEP 7 online help
Section Installation (Page 125)
Section Wiring (Page 148)
Section Removing/inserting a SIMATIC
memory card on the CPU (Page 258)
Section First power-on of the CPU
(Page 261)
The meaning of the LEDs can be found in
the manuals of the modules.
Section CPU display (Page 290)
Online and diagnostics functions in
STEP 7
The following functions are helpful:
Monitoring and modifying tags, testing
with program status, forcing, modifying
the outputs in STOP mode. Section Test
and service functions (Page 328)
257

Advertisement

Table of Contents
loading

Table of Contents