Omron CompoNet MX2 Series User Manual page 113

Inverter, communications unit
Hide thumbs Also See for CompoNet MX2 Series:
Table of Contents

Advertisement

Precautions for Correct Use
Precautions for Correct Use
The Register No. and read/write data are the same as those for Modbus communication. For
these settings, refer to Section 6-8 Modbus Communication (Modbus-RTU) Data List of the
MX2 User's Manual (Cat. No. I570) and 8-5 Modbus Communication Register Number List of
the RX User's Manual (Cat. No. I578).
The error codes for the Special IO operation are listed below.
 Special Remote Input Error Codes
Error
Code
01 hex
Function Code Error
02 hex
Register No. Error
04 hex
Slave Device Error
21 hex
Data Setting Error
22 hex
Write Mode Error
23 hex
Register Size Error
Precautions for Correct Use
Precautions for Correct Use
If a Special I/O read/write error occurs, the most significant bit (word address n, bit 7) of the
Function Code turns ON. Prepare a program that starts error processing from this bit on the
host.
Reading/Writing Input/Output Bit Data (Modbus Coil Information)
In Modbus communication, the MX2/RX-series inverters set control input, status monitor, or other bit
information as coil information. This means that you cannot set/check data by reading/writing from/to
communications registers.
Use the following registers provided to enable reading/writing of input and output bit information.
 Register No. 1F01 hex for CompoNet output (Inverter control input)
Bit
15
Name
Value
0
Opr
RUN command (0: Stop/1: Run)
Dir
Rotation direction command
(0: Forward/1: Reverse)
EXT
External trip
RS
Reset
In1
General-purpose output terminal [1]
In2
General-purpose output terminal [2]
CompoNet Communications Unit User's Manual (I582-E1)
Name
14
13
12
11
10
In8
In7
In6
In5
In4
0
0
0
0
0
Description
A code other than 03/10/43 or 50 hex is set as function code.
The specified Register No. does not exist.
The Option Board failed to communicate with the inverter.
An upper or lower limit for the write data setting range is
exceeded.
Writing to a register that is write-prohibited or in a read-only
state (for example, during operation).
Reading/Writing 2-byte data from/to a 4-byte register or 4-byte
data from/to a 2-byte register.
9
8
7
6
5
In3
In2
In1
0
0
0
0
0
In3
General-purpose output terminal [3]
In4
General-purpose output terminal [4]
In5
General-purpose output terminal [5]
In6
General-purpose output terminal [6]
In7
General-purpose output terminal [7]
In8
General-purpose output terminal [8]
4 Remote I/O
4
3
2
1
0
RS
EXT
Dir
Opr
0
0
0
0
0
4 - 19
4

Advertisement

Table of Contents
loading

Table of Contents