Specifications - Trane Air-Fi WCS-SB Installation, Operation And Maintenance Manual

Wireless system
Table of Contents

Advertisement

Specifications

Table 4.
WCI and WCS specifications
General Specifications
Operating Temperature
Storage Temperature
Storage and Operating Humidity Range
Housing Material
Range
(a)
Output Power
Radio Frequency
Radio Channels
FCC ID#
IC ID#
Wireless Communications Interface (WCI) Specifications
Voltage
Power Consumption
Indoor Mounting
Outdoor Mounting
Wireless Protocol
Wireless Communications Sensor (WCS) General Specifications
Accuracy
Resolution
Sampling Rate (Temperature)
Setpoint Functional Range
Transmit Trigger
Sensor Battery (Energizer® L91)
Address Range
Maximum Time Between Transmissions
Minimum Time Between Transmissions
Mounting
BAS-SVX40K-EN
WCI -40 to 158 degrees ºF (-40 to 70 degrees ºC)
WCS-SB, SD, SO, SCO
and SB/R internal sensor 32 to 122 ºF (0 to 50 degrees ºC)
2
WCS-SB/R remote sensor -58 to 122 degrees ºF (-50 to 50 degrees ºC)
-40 to 185º F (-40 to 85° C)
5% to 95% relative humidity (RH), non-condensing
Polycarbonate/ABS (suitable for plenum mounting), UV protected, UL 94: 5 VA flammability rating
Open range: 2,500 ft (762 m) with packet error rate of 2%. Indoor: Typical range is 200 ft (61 m); actual
range is dependent on the environment. See BAS-SVX55* for more detail.
100 mW
2.4 GHz (IEEE Std 802.15.4-2003 compliant) (2405–2480 MHz, 5 MHz spacing)
16
W7Z-ZICM357SP2
8254A-ZICM357SP2-1
24 Vac/Vdc nominal ±10%. If using 24 Vdc, polarity must be maintained.
<1.0 VA
Fits a standard 2 in. by 4 in. junction box (vertical mount only). Mounting holes are spaced 3.2 in. (83 mm)
apart on vertical center line. Includes mounting screws for junction box or wall anchors for sheet-rock
walls. Overall dimensions: 2.9 in. (74 mm) by 4.7 in. (119 mm).
Position enclosure in desired flat mounting location and mount using four (4) #8 sheet metal screws with
the conduit connection pointing down. If not mounted to the HVAC equipment exterior wall, the conduit
connection on the bottom of the enclosure is also available. Please note that the supplied plug must be
installed into the unused conduit connection.
Overall dimensions: 3.9 in. (98 mm) by 6.4 in. (163 mm) by 1.7 in. (42 mm).
ANSI/ASHRAE Standard 135-2016 (BACnet® / Zigbee®)
BACnet® is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning
Engineers (ASHRAE)
ZigBee® is a registered trademark of the ZigBee Alliance
0.5ºF for a range of 55 to 85°F (12.8 to 29.4°C)
+0.125ºF over a range of 60ºF to 80ºF (15.56°C to 26.67°C)/±0.25°F outside this range
30 seconds
45ºF to 95ºF (7.22ºC to 35ºC)
0.2ºF change or once every 15 minutes
Two (2) AA lithium 1.5 V batteries, 2800 mAh with an expected life of 15 years under typical operating
conditions for non-CO
WCS. For WCS-SCO
2
occupied 10 hours a day, five days per week. For buildings occupied 24 hours a day/seven days a week,
the expected battery life is 10 years.
001 to 999 for UC controllers, 001 to 996 for Symbio™ controllers.
15 minutes
10 seconds. Time between transmissions can be shorter during user interaction.
Fits a standard 2 in. by 4 in. junction box (vertical mount only). Mounting holes are spaced 3.2 in. (83 mm)
apart on vertical
center line. Includes mounting screws for junction box and wall anchors for sheet-rock walls.
Overall dimensions: 2.9 in. (74 mm) by 4.7 in. (119 mm)
, expected battery life is 15 years for commercial buildings
2
Overview
17

Hide quick links: