Overview

This section provides an overview of Trane Air-Fi® wireless systems and the two Trane Air-Fi® wireless
devices.
Air-Fi® Wireless Communications Interface (WCI)
The Air-Fi® Wireless Communications Interface (WCI) enables wireless communications between
system controls, unit controls, and wireless sensors for Trane® control products that use the BACnet®
protocol. The WCI replaces the need for communications wire in all system applications.
The WCI is available in three configurations:
Air-Fi® Wireless Communications Sensor (WCS)
The Air-Fi® Wireless Communications Sensor (WCS) is compatible with any Trane controller that uses
a WCI. The WCS provides the same functions as many currently available Trane wired sensors. No
further software or hardware is necessary for site evaluation, installation, or maintenance. Space
temperature is standard on all models. (A service tool cannot be connected to a Trane wireless sensor.)
Six WCS models are available:
In most applications, one WCS sensor will be used per WCI acting as a router. However, up to 6 WCS
sensors can be associated to a single equipment controller or BCI/BCI2.
See

Compatibility with Previous Generation Wireless Zone Products

Our previous line of wireless zone sensors (WZS, WTS, and WDS) are not compatible with the Air-Fi
Wireless Communications Interface (WCI).
The new Air-Fi Wireless Communications Sensor (WCS) are compatible with old WCIs that have
updated firmware.
WCS-SO and WCS-SCO
Requirements for Devices on an Air-Fi® Network," p.

Wired Zone Sensors

Wired zone sensors can be used with Air-Fi wireless systems.
Devices Supported by Air-Fi® Wireless Systems
BAS-SVX40K-EN
The universal model is the most common. It installs the same as a wired zone sensor in indoor
applications.
The outdoor model is housed in an enclosure suitable for outdoor environments. It is usually used
on equipment above the roof deck.
The flush mount model is used on fan coils, blower coils, and unit ventilators.
WCS-SB: Base model, has no exposed display or user interface
WCS-SD: Digital display
WCS-SCO
: CO
with occupancy
2
2
WCS-SO: Occupancy
WCS-SB/R: Refrigeration and freezer monitoring sensor
WCS-SH: 2% relative humidity sensor module, can be field installed inside either the WCS-SD,
WCS-SB, WCS-SO, WCS-SCO
"Wireless Sensor Setup," p. 88
require minimum unit controller firmware as described in
2
Tracer® SC/SC+ system controller
Tracer® UC210 programmable controller
Tracer® UC400 programmable controller
, WCS-SB/R
2
for details on how to set this up.