Trane Air-Fi WCS-SB Installation, Operation And Maintenance Manual page 37

Wireless system
Table of Contents

Advertisement

5. Press the up/down arrow buttons to set the right number to match the corresponding network (NET).
6. Press the right arrow button to proceed to the next address setting. Three numbers appear at the
7. Press the up/down arrow buttons to set the flashing number to match the first number of the rotary
8. Press the right arrow button to make the second number flash.
9. Set the second number as for the first. Repeat the same procedure for the third number.
10. If only one WCS is associated with a WCI, proceed to the last step.
BAS-SVX40K-EN
top of the display, with the left number flashing. At the bottom of the display, the letters U C indicate
that the three numbers correspond to the three-digit address of the unit controller.
Figure 25. Setting the UC rotary address
address setting of the associated unit controller.
If multiple WCSs (maximum of 6) are associated with the same WCI, each WCS must have a unique
sensor address. WCS address numbers must be consecutive.
Note: The total number of associated sensors affects the total number of WCIs that can
communicate on the network. Refer to
Allowed," p.
10.
For multiple WCS installations, press the right arrow button to proceed to the WCS address setting.
One number (default is "1") will appear at the top of the display. At the bottom of the display, the
letters S n indicate that the top number corresponds to a sensor address.
Note: Additional setup is required in Tracer TU for multiple WCS installations. For details, see
the Tracer® TU Service Tool with a Wireless Network," p.
WCS-SB/SD Installation
"Maximum Number of Air-Fi® Devices and Networks
78.
"Using
37