Using the Tracer® TU Service Tool with a Wireless Network
11. Create an analog output point called Space Temp Average. This point will store the average
12. Create a refrigeration monitoring analog input point by clicking Create.
13. Name the point, then select the reference as Sensor 3 > Space Temperature. This creates the point
14. Check the Add to SC Temp box if the refrigerator temperature point is desired to be viewed at the
96
temperature value for the two space sensors just created. Select Temperature under Dimensionality.
No reference is needed. This point will be needed when writing the TGP2 averaging program in Step
17.
reference "wci.sensors.3.spaceTemp". This point will not be part of the TGP2 averaging program.
It will display individually.
SC level.
BAS-SVX40K-EN