Trane Air-Fi WCS-SB Installation, Operation And Maintenance Manual page 95

Wireless system
Table of Contents

Advertisement

steps are not taken.
In this example there are three sensors; two space temperature sensors and one refrigerator sensor.
The two Space Temperature sensors will be addressed as Sensor 1 and Sensor 2. The refrigerator/
freezer sensor will be addressed as Sensor 3. All sensors are associated to the same unit controller,
and the desire is to have the two space sensors averaging, and the refrigerator sensor not part of the
averaging.
1. Connect Tracer TU to the unit controller using any connection method.
2. Using Tracer TU, go to the Controller Settings tab. Under the Wireless Sensor Configuration pane,
3. Select the number of wireless sensors under the Wireless Sensors drop down. In this example it is
4. Click Send to Device.
5. Go to the Analog tab.
6. Create a new analog input point called Space Temperature 1.
7. For the reference select Sensor 1 > Space Temperature. This will create a reference of "wci.
8. Hit OK, then OK again, then Send to Device.
9. Create a second analog input point called Space Temperature 2.
10. For the reference select Sensor 2 > Space Temperature. This creates the point reference "wci.
BAS-SVX40K-EN
Using the Tracer® TU Service Tool with a Wireless Network
uncheck the Enable Wireless Space Sensor box. Unchecking this box will prevent newly created
references from being replaced with default averaging references if the unit controller is power
cycled.
3.
sensors.1.spaceTemp". You will use this point in TGP2 to create a space temp averaging program.
sensors.2.spaceTemp". You will use this point in TGP2 to create a space temp averaging program.
95