Specifications

The following table presents specifications for all models of the wireless sensor sets.
Sensor operating temperature
Receiver operating temperature
Storage temperature
Storage and operating humidity range
Accuracy
Resolution
Setpoint functional range (WZS only)
Setpoint functional range (WDS only)
Setpoint thumb wheel markings (WZS only)
Receiver voltage
Receiver power consumption
Housing
Mounting
Sensor battery
Range
Output power
Radio frequency
Radio channels
Address range
Minimum time between transmissions
Maximum time between transmissions
(a) Range values are estimated transmission distances for satisfactory operation. Actual distance is job specific and
BAS-SVX04C-EN • Wireless Sensors
(a)
must be determined during site evaluation.
32 to 122ºF (0 to 50ºC)
-40 to 158ºF (-40 to 70ºC)
-40 to 185ºF (-40 to 85°C)
5% to 95%, non-condensing
0.5 °F over a range of 55 to 85°F (12.8 to 29.4°C)
0.125ºF over a range of 60 to 80ºF
(15.56 to 26.67°C)
0.25ºF when outside this range
45 to 95ºF (7.22 to 35ºC)
50 to 89.6ºF (10 to 32ºC)
50 to 85ºF (stamped every 5ºF) and *, **
11 to 29ºC (stamped every 3ºC) and *, **
24 V nominal ac/dc ± 10%
<1 VA
Polycarbonate/ABS blend, UV protected, UL 94-5VA
flammability rating, suitable for application in a
plenum
3.24 in (8.26 cm) for 2 mounting screws (supplied)
(2) AA, 1.5 V, 2800 mAh, lithium, 5-year life, UL listed
Open range: 2,500 ft (762 m)
(packet error rate = 2%)
Usable: 200 ft (61 m)
Typical: 75 ft (23 m)
100 mW
2.4 GHz (IEEE Std 802.15.4-2003 compliant)
(2405–2480 MHz, 5 MHz spacing)
16
000–999
30 seconds
15 minutes