The following table provides specifications for all models of the wireless sensor sets.
Sensor operating temperature
Receiver operating temperature
Storage temperature
Storage and operating humidity range
Accuracy
Resolution
Setpoint functional range (WZS only)
Setpoint functional range (WDS only)
Setpoint thumb wheel markings (WZS only)
Receiver voltage
Receiver power consumption
Housing
Mounting
Sensor battery
(a)
Range
Output power
Radio frequency
Radio channels
Address range
Minimum time between transmissions
Maximum time between transmissions
(a) Range values are estimated transmission distances for satisfactory operation. Actual distance is job specific and must be determined during site eval-
uation.
BAS-SVX04G-EN
32 to 122ºF (0 to 50ºC)
-40 to 158ºF (-40 to 70ºC)
-40 to 185ºF (-40 to 85°C)
5% to 95%, non-condensing
0.5 °F over a range of 55 to 85°F (12.8 to 29.4°C)
0.125ºF over a range of 60 to 80ºF (15.56 to 26.67°C)
0.25ºF when outside this range
45ºF to 95ºF (7.2ºC to 35ºC)
Single setpoint: 50ºF to 89.6ºF (10ºC to 32ºC)
Dual setpoint: 56ºF to 89.6ºF (13.3ºC to 32ºC)
50 to 85ºF (stamped every 5ºF) and *, **
11 to 29ºC (stamped every 3ºC) and *, **
24 V nominal ac/dc ± 10%
<1 VA
Polycarbonate/ABS blend, UV protected, UL 94-5VA flammability rating,
suitable for application in a plenum
3.24 in (8.26 cm) for 2 mounting screws (supplied)
(2) AA, 1.5 V, 2800 mAh, lithium, 5-year life, UL listed
Open range: 2,500 ft (762 m)
(packet error rate = 2%)
Usable: 200 ft (61 m)
Typical: 75 ft (23 m)
100 mW
2.4 GHz (IEEE Std 802.15.4-2003 compliant) 
(2405–2480 MHz, 5 MHz spacing)
16
000–999
30 seconds
15 minutes
45