Trane Air-Fi WCS-SB Installation, Operation And Maintenance Manual page 38

Wireless system
Table of Contents

Advertisement

WCS-SB/SD Installation
11. Press the up/down arrow button to set a unique sensor address (1 through 6) for the WCS.
12. Addressing is finished. Press the center button to return to the normal display.
Note: To verify addressing, press and hold the Address button until the display changes to addressing
The following figure shows the same Air-Fi Wireless figure shown in
WCSs added.
Figure 27. Air-Fi addressing example: WCIs and WCSs
Group and
network
addresses
must match.
Controller
addresses
must
match.
38
Figure 26. Setting a unique sensor address
mode. Then use the right arrow button to scroll through the settings.
Tracer SC+
group 1
Network 1
1
1
GRP NET
WCI
1
1
1
1
GRP NET
GRP
NET
WCI
WCI
Controller
Controller
102
101
WCS
WCS
gn: 11
gn: 11
UC: 101
UC: 102
Sn: 1
Sn: 1
Sensor addresses default to 1. If multiple sensors are wired to a UC/BCI, each sensor must have a unique address.
WCI addressing
Network 2
Network 1
GRP
NET
1
2
GRP NET
WCI
1
2
1
2
2
1
GRP NET
GRP NET
GRP NET
WCI
WCI
WCI
Controller
Controller
Controller
201
202
301
WCS
WCS
WCS
gn: 12
gn: 12
gn: 21
UC: 202
UC: 201
UC: 301
Sn: 1
Sn: 1
Sn: 1
"WCI Addressing," p.
Tracer SC+
group 2
Network 2
2
1
2
2
GRP NET
GRP NET
WCI
WCI
2
1
2
2
2
GRP NET
GRP NET
GRP NET
WCI
WCI
WCI
Controller
Controller
Controller
401
402
302
WCS
WCS
WCS
gn: 22
gn: 22
UC: 402
gn: 21
UC: 401
Sn: 1
UC: 302
Sn: 1
Sn: 1
UC/BCI 402 has two sensors
connected to it. Therefore,
the address of the second
sensor is set to "2."
25, but with
2
WCS
gn: 22
UC: 402
Sn: 2
BAS-SVX40K-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents