Overview
Table 6. Wireless sensing specifications
Sensor Type
Temperature
Relative Humidity
CO
2
Occupancy
20
Sampling Rate
30 seconds
30 seconds
Occupied — 5 minutes
Unoccupied — 15 minutes
Continuous
Change of Value Trigger/Delay
0.2°F
1% RH
50 ppm
Unoccupied to Occupied:
•
Transmits change of state within
30 seconds.
Occupied to Unoccupied:
•
5–10 minutes delay (not
adjustable).
•
Sends unoccupied message
after 5–10 minutes without
motion.
Heartbeat
15 minutes
BAS-SVX40K-EN