6. Press and hold the ADDR button for 3 seconds to exit the addressing mode.
You can verify your address settings by once again pressing and holding the ADDR button for 3
seconds to return to addressing mode. Use the NEXT button to scroll through the settings.
The following figure shows the Air-Fi Wireless network example with sensors added.
Figure 33. Air-Fi Wireless network with sensors added
Group and
network
addresses
must match.
Controller
addresses
must
match.
BAS-SVX40K-EN
Notes:
•
The total number of associated sensors affects the total number of WCIs that can
communicate on the network. Refer to
Networks Allowed," p.
•
Additional setup is required in Tracer TU for multiple sensor installations. For details, see
"Using the Tracer® TU Service Tool with a Wireless Network," p.
Tracer SC+
group 1
Network 1
1
1
GRP NET
WCI
1
1
1
1
GRP
GRP NET
NET
WCI
WCI
Controller
Controller
102
101
WCS
WCS
gn: 11
gn: 11
UC: 101
UC: 102
Sn: 1
Sn: 1
Sensor addresses default to 1. If multiple sensors are wired to a UC/BCI-R each sensor must have a unique address.
WCS–SO/SCO
"Maximum Number of Air-Fi® Devices and
10.
WCI addressing
Network 2
Network 1
GRP
NET
1
2
GRP NET
WCI
1
2
1
2
2
1
GRP NET
GRP NET
GRP NET
WCI
WCI
WCI
Controller
Controller
Controller
201
202
301
WCS
WCS
WCS
gn: 12
gn: 12
gn: 21
UC: 202
UC: 201
UC: 301
Sn: 1
Sn: 1
Sn: 1
and –SB/R Installation
2
78.
Tracer SC+
group 2
Network 2
2
1
2
2
GRP NET
GRP NET
WCI
WCI
2
1
2
2
2
GRP NET
GRP NET
GRP NET
WCI
WCI
WCI
Controller
Controller
Controller
401
402
302
WCS
WCS
gn: 22
WCS
gn: 22
UC: 402
gn: 21
UC: 401
Sn: 1
UC: 302
Sn: 1
Sn: 1
Controller 402 has two sensors
connected to it. Therefore,
the address of the second
sensor is set to "2."
2
WCS
gn: 22
UC: 402
Sn: 2
43