6. Press and hold the ADDR button for 3 seconds to exit the addressing mode.
You can verify your address settings by once again pressing and holding the ADDR button for 3
seconds to return to addressing mode. Use the NEXT button to scroll through the settings.
The following figure shows the Air-Fi Wireless network example with sensors added.
Figure 33. Air-Fi Wireless network with sensors added
Group and
network
addresses
must match.
Controller
addresses
must
match.
BAS-SVX40K-EN
Notes:
The total number of associated sensors affects the total number of WCIs that can
communicate on the network. Refer to
Networks Allowed," p.
Additional setup is required in Tracer TU for multiple sensor installations. For details, see
"Using the Tracer® TU Service Tool with a Wireless Network," p.
Tracer SC+
group 1
Network 1
1
1
GRP NET
WCI
1
1
1
1
GRP
GRP NET
NET
WCI
WCI
Controller
Controller
102
101
WCS
WCS
gn: 11
gn: 11
UC: 101
UC: 102
Sn: 1
Sn: 1
Sensor addresses default to 1. If multiple sensors are wired to a UC/BCI-R each sensor must have a unique address.
WCS–SO/SCO
"Maximum Number of Air-Fi® Devices and
10.
WCI addressing
Network 2
Network 1
GRP
NET
1
2
GRP NET
WCI
1
2
1
2
2
1
GRP NET
GRP NET
GRP NET
WCI
WCI
WCI
Controller
Controller
Controller
201
202
301
WCS
WCS
WCS
gn: 12
gn: 12
gn: 21
UC: 202
UC: 201
UC: 301
Sn: 1
Sn: 1
Sn: 1
and –SB/R Installation
2
78.
Tracer SC+
group 2
Network 2
2
1
2
2
GRP NET
GRP NET
WCI
WCI
2
1
2
2
2
GRP NET
GRP NET
GRP NET
WCI
WCI
WCI
Controller
Controller
Controller
401
402
302
WCS
WCS
gn: 22
WCS
gn: 22
UC: 402
gn: 21
UC: 401
Sn: 1
UC: 302
Sn: 1
Sn: 1
Controller 402 has two sensors
connected to it. Therefore,
the address of the second
sensor is set to "2."
2
WCS
gn: 22
UC: 402
Sn: 2
43