Rh Sensor Module Installation - Trane Air-Fi WCS-SB Installation, Operation And Maintenance Manual

Wireless system
Table of Contents

Advertisement

WCS–SO/SCO
and –SB/R Installation
2
Figure 36. Sensor eye turns red when motion is detected
This adjustment is necessary for both WCS-SO and WCS-SCO
a built-in occupancy sensor. It is used to reduce the number of CO
unoccupied to conserve battery life.
It is assumed the sensor has been mounted in a position where occupancy or CO
The maximum range for the occupancy sensor is 32 feet (10 meters). Set the sensor in Motion Test
mode and wait for the red light to go off. Walk through the area and watch the sensor eye illuminate red
indicating your presence is sensed. Make any mounting adjustments to achieve the best overall position
of the sensor where it will detect human traffic.
Reference the occupancy sensor coverage pattern below to help determine the best mounting position.
Figure 37. WCS-SO sensor coverage patterns
If more time is needed than the default 120 seconds, you can press the UP arrow to add time in 30
second increments to a maximum of 600 seconds.

RH Sensor Module Installation

A 2% relative humidity (RH) sensor module, available as a separate part (X13790973030; model WCS-
SH), can be installed on a WCS either before or after the WCS is powered up as shown in the following
figure. If the RH sensor module is installed on the WCS after power-up, the WCS will detect it when you
pull out the battery to shut off the sensor, then put the battery back in to turn the sensor on.