Regular Inspections
Inspection items
Power Supply
Ambient Temperature
Ambient Humidity
Installation
Note
150
To maintain the V530-C300E in the best condition, perform the fol-
lowing regularly.
• Lightly wipe off dirt with a soft cloth.
• Clean the lens and indicators with a cloth for a lens or air brush.
The voltage measured at the power supply
terminals on the terminal block must be
24 VDC (+10%, –15%).
The operating ambient temperature inside
the cabinet must be between 0 to +38
The operating ambient humidity inside the
cabinet must be between 35 to +85%.
Each cable connector must be correctly
inserted and locked.
1.
Turn OFF the power and take safety precautions before conduct-
ing inspections.
2.
Do not use thinners or benzene.
Details
Section 7
Required tools
Circuit Tester
Thermometer
C.
Hygrometer
Phillips screw driver

Advertisement