Slave Unit Allocations For Communications Mode Number 8 - Omron CJ Series Operation Manual

Machine automation controller
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

5-4-5

Slave Unit Allocations for Communications Mode Number 8

When using communications mode 8, I/O ports are not used. I/O data for the CompoNet Master Unit is
assigned in software settings directly to any locations in the memory used for CJ-series Units (any
addresses in the CIO, WR, HR, or DM Area).
The software settings are made from the CX-Integrator. Slave Unit allocations are made for WORD IN,
WORD OUT, BitIN, BitOUT, Connect Flags, and Communication Error Flags for each Word or Bit Slave
Unit. To access the memory locations that were specified in the software settings from the user pro-
gram, you use user-defined variables with AT specifications to the memory used for CJ-series Units.
CX-Integrator
Software Setting Table
Area
WORD OUT
WORD IN
BIT OUT
BIT IN
Connect/Communication
Error Flags: Word Units
Connect/Communication
Error Flags: Bit Units
For the allocations of Slave Unit I/O data in communications mode number 8, refer to Memory Alloca-
tions for Communications Mode Number 8, below.
Refer to the SYSMAC CS/CJ/CP/NSJ Series CX-Integrator Version 2.3 Operation Manual (Cat. No.
W464) for the editing procedures for software setting tables.
CJ-series CompoNet Master Unit Operation Manual for NJ-series CPU Unit (Cat. No. W493)
NJ-series
CPU Unit
Start
Number
area/address
of nodes
Mode No. = 8
5 Remote I/O Communications
Memory used for the CJ-series
User-set location
Word IN Area
:
User-set location
Word OUT Area
Word Connect Status
User-set location
User-set location
Bit IN Area
:
User-set location
Bit OUT area
User-set location
Bit Connect Status
The addresses and areas for the Word OUT
CompoNet Master
Area, Word IN Area, BitOUT Area, BitIN Area,
Unit
Connect Flags, and Communication Error
Flags are set for each Word Unit and Bit Unit.
CompoNet
Bit Slaves
Word Slaves
5
5-49