1 Introduction
9.
Connect the computer with the Sysmac Studio or CX-Integrator to the
USB port or built-in EtherNet/IP port on the CPU Unit of the Controller
where the Master Unit is mounted.
10. Turn ON the power supply to the Controller.
11. Download the project from the Sysmac Studio to the CPU Unit.
12. Using the CX-Integrator, edit and download the Master Unit device
parameters.
1. Go online with the CPU Unit of the Controller to which the Mas-
ter Unit is mounted.
2. In the Online Connection Information Window, right-click the
Master Unit under the connected PLC, and then select Con-
nect.
3. Right-click the Master Unit under the connected PLC, and
select Transfer [Network to Computer].
4. Double-click the Master Unit in the Network Configuration Win-
dow, and then edit and download the device parameters.
13. Reset the Controller or cycle the power supply to the Controller.
14. Remote I/O communications will start when all registered Slave Units are
participating.
15. Using the CX-Integrator, monitor the participation status of the Slave
Units.
1. While online, upload the network configuration.
2. Right-click the Master Unit in the Network Configuration Win-
dow and select Monitor to monitor the participation status on
the Status/Unit Status Tab Page.
1-24
CJ-series CompoNet Master Unit Operation Manual for NJ-series CPU Unit (Cat. No. W493)
@
... CX-Integrator Version 2.
Operation Manual (Cat. No.
W464)
... Sysmac Studio Version 1
Operation Manual (Cat. No.
W504)