Flat Cable Ii - Omron CJ Series Operation Manual

Machine automation controller
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

2
Attaching the Housing
(1) Confirm the colors again, and temporarily secure the housing to the cover.
3
Pressure-welding the Connector
Use the DWT-A01 Pliers to pressure-weld the connector.
(1) Align the center (see arrows) of the connector cover with the center of the pressure-
welding block on the DWT-A01 Pliers.
(2) Squeeze firmly on the Pliers until the lock on the connector clicks into place.
Special Tool
(DWT-A01 Pliers)
Note After pressure-welding the Cable, confirm that the Cable is properly pressure-welded. The
lock on the housing must be completely engaged with the cover.

4-3-3 Flat Cable II

Preparing and Mounting DCN5-TR4 Flat Connector Sockets
• Component Names
1
Cutting the Cable
This step is required only for extending the cable or connecting a Terminating Resistor.
At the tip of cable, cut the cable perpendicular to the cable length. To prevent short-circuits, use
a sharp cutting tool such as nipper. Confirm there is no remaining wire coming out.
CJ-series CompoNet Master Unit Operation Manual for NJ-series CPU Unit (Cat. No. W493)
Connector cover
Cover
4 Installation and Wiring
4
4-25