MECHATROLINK Communication

6.5 Power ON Sequence (Communication Sequence)

6
The following is a typical power ON sequence (communication sequence).
1. Turn ON the control power supply.
2. Make communication connection (CONNECT command).
When communication connection has been completed, confirm the following: COMRDY=1
and SVALM=0. Also confirm the MECHATROLINK version.
3. Check device ID, etc.
Confirm that the ID is "SGD-
4. Write required parameters by PRM_WR command. (Set up the equipment (CONFIG com-
mand))
5. Turn encoder (sensor) power ON (SENS_ON command).
When the power has been turned ON, confirm the following status: COMRDY=1.
6. Main circuit ON (SV_ON command).
When the main circuit has been turned ON, confirm the following status: SVON=1.
7. Operation starts.
:
8. Main circuit OFF (SV_OFF command).
When the main circuit has been turned OFF, confirm the following status: SVON=0.
9. Communication disconnected (DISCONNECT command)
10. Turn control power supply OFF.
After turning ON the control power, transfer the NOP command or CONNECT command
until communication connection has been completed.
N". Also confirm the software version.
***