Omron ZJ-SD Series User Manual page 76

Smart electrostatic sensor
Table of Contents

Advertisement

Section 5
Using the Hold Functions
Setting the Delay Time
Set the delay time function, for example, to ignore measured values immediately after a
hold trigger is detected in order to avoid fluctuation of signals near the sensing object
boundary.
The delay time (the delay between detection of the trigger and start of sampling) and
the sampling period can be set.
The default delay time setting is OFF.
• Make the sum of the delay time and sampling period less than the trigger detection interval.
• If the next trigger input for measurement is detected before the sum of the delay time and sampling
period have elapsed, that trigger input is ignored and is not reflected in sampling.
• Triggers are detected when the hold trigger and trigger condition is satisfied (ex: when the timing
input turns ON)
Timing input
Moving to the delay hold (H-DLY)
1.
Use the LEFT and RIGHT keys to display
[H-DLY] on the main display.
H-DLY is not displayed if the hold condition is set to
[OFF].
2.
Press the UP or DOWN key.
The sub-display flashes.
3.
Use the UP and DOWN keys to display [ON].
4.
Press the ENT key.
The H-DLY function can now be set.
ZJ-SD
62
User's Manual
Delay time
Sampling period
ON
OFF
Ignored
Delay time
Accepted

Advertisement

Table of Contents
loading

Table of Contents