50/85
Bosch Rexroth AG
Errors: Reporting and troubleshooting
Code +
Error cause
AddValue
0x2382
There is at least still one output
+ 0x02F2
with a parameterized switch-off
delay in the switch-off process
0x6320
The parameterization of two rela‐
+ 0x023X
ted outputs does not correspond
to the dual-channel setting
0x6320
The parameterized switch-off de‐
+ 0x02EX
lay time is outside the permitted
value range
0x6320
For outputs parameterized as
+ 0x029X
dual-channel, different settings
than for the switch-off delay were
assigned
0x6320
Calculated and received check‐
+ 0x03F2
sum of the parameter data does
not match
0x6320
Device ID is incorrect or wrong
+ 0x03FB
module is used.
9.2.5

General errors

Code
Error cause
0x4210
Critical module temper‐
ature
0xA012 Possible error causes:
Application is not
ready on the
module
Hardware error
TUNID (DIP
switch) was
changed at run‐
time
9.3

CSos errors

IndraControl S20 Module With Safe Digital Outputs S20-SSDO-8/3
LED
Description, effect
FS
The module is retained in the
flash‐
safe state.
ing
Tab. 9-11:
Parameterization errors (cannot be acknowledged)
LED
Description, effect
-
The module temperature reached a criti‐
cal value. The switch-off is imminent. If
the temperature increases more, the
module goes into the safe state using the
device firmware.
FS on
The communication to a safe parent con‐
trol is locked. The module goes into the
safe state.
Tab. 9-12:
General errors
The following errors can occur additionally:
For errors of the CSos system, refer to
and device parameters" on page
DOK-CONTRL-S20*SSDO*8*-AP02-EN-P
Solution
Wait for the completion of the
switch-off process and send param‐
eter data again to the module.
Correct the value and send the pa‐
rameter data again to the module.
Correct the value and send the pa‐
rameter data again to the module.
Correct the value and send the pa‐
rameter data again to the module.
Check checksum and send param‐
eter data again to the module.
Check that the correct module is
used. If the error cannot be elimina‐
ted, contact Bosch Rexroth.
Acknowledgement, remedy
Check the ambient conditions and
switching frequency and modify
them if required.
This diagnostic message can be
acknowledged. The acknowledge‐
ment deletes the diagnostic mes‐
sage.
This diagnostic message cannot be
acknowledged. Execute power-up.
If the error message is output
again, the module is defective and
has to be replaced.
chapter 13 "CSos parameters