DOK-CONTRL-S20*SSDO*8*-AP02-EN-P
IndraControl S20 Module With Safe Digital Outputs S20-SSDO-8/3
3

Product description

3.1

Brief module description

3.2

Module structure

The module S20-SSDO-8/3 is a safe output module to be used in an
IndraControl S20 station at any position in a Sercos I/O system. The module
can only be used together with a safety control. The safe connection is estab‐
lished via the safe bus protocol CSos (CIP Safety on Sercos).
Set the TUNID (SNN and SDID) for the Csos device via a DIP switch.
The module is provided with four safe digital outputs for the dual-channel as‐
signment or eight digital outputs for the single-channel assignment.
The outputs can be parameterized user-specifically and allow the integration
of actuators into the safe Csos system.
In the Csos system, safety categories with the following requirements can be
met with the module depending on the application conditions:
Up to SIL 3 acc. to IEC 61508
Up to SILCL 3 acc. to EN 62061
Up to cat. 4/PL e acc. to EN ISO 13849-1
1
1
Bus base module
2
Electronics module
3
Plug to connect the supply voltage
4
Color code of the function
5
Peripheral connector
6
Diagnostic and status displays
7
DIP switch
Fig. 3-1:
Module structure
For more information on the settings of the DIP switches, refer to
chapter 5.1.3 "Setting DIP switch" on page
Bosch Rexroth AG