DOK-CONTRL-S20*SSDO*8*-AP02-EN-P
IndraControl S20 Module With Safe Digital Outputs S20-SSDO-8/3
Disabling the outputs
By the safe control
After a bus error
After a short circuit, cross-fault,
power supply failure or hardware
error
Tab. 6-2:
Disabling the outputs depends on the triggering event and the param‐
eterization
WARNING
Observe the following for stop category 1:
●
The respective outputs only go into the safe state after the switch-off de‐
lay.
●
If an error occurs (except for bus errors), the respective outputs are im‐
mediately switched off (without delay). In this case, only stop category 0
is supported.
WARNING
For the safety distances, observe the selected switch-off delay.
Note the following when switching off:
●
Switching off can be canceled by switching on the output again.
●
When changing the module parameterization, the changed parameteri‐
zation is only applied after all outputs are switched off.
●
When changing the parameterization before the switch-off is completed,
a diagnostic message is generated.
●
Due to a changed parameterization, the switch-off delay startup can be
delayed.
Validate after changing the parameterization.
Bosch Rexroth AG
Parameterizing the module
Effect of the set
Disabling the outputs
switch-off delay
Yes
After the set switch-off delay ex‐
pired
Yes
After the set switch-off delay ex‐
pired
No
Immediately (only stop catego‐
ry 0)
Machine lagging due to stop category 1
Incorrect safety distances due to an incorrect‐
ly selected switch-off delay
31/85