DOK-CONTRL-S20*SSDO*8*-AP02-EN-P
IndraControl S20 Module With Safe Digital Outputs S20-SSDO-8/3
Disabling the outputs
By the safe control
After a bus error
After a short circuit, cross-fault,
power supply failure or hardware
error
Tab. 6-2:
Disabling the outputs depends on the triggering event and the param‐
eterization
WARNING
Observe the following for stop category 1:
The respective outputs only go into the safe state after the switch-off de‐
lay.
If an error occurs (except for bus errors), the respective outputs are im‐
mediately switched off (without delay). In this case, only stop category 0
is supported.
WARNING
For the safety distances, observe the selected switch-off delay.
Note the following when switching off:
Switching off can be canceled by switching on the output again.
When changing the module parameterization, the changed parameteri‐
zation is only applied after all outputs are switched off.
When changing the parameterization before the switch-off is completed,
a diagnostic message is generated.
Due to a changed parameterization, the switch-off delay startup can be
delayed.
Validate after changing the parameterization.
Bosch Rexroth AG
Parameterizing the module
Effect of the set
Disabling the outputs
switch-off delay
Yes
After the set switch-off delay ex‐
pired
Yes
After the set switch-off delay ex‐
pired
No
Immediately (only stop catego‐
ry 0)
Machine lagging due to stop category 1
Incorrect safety distances due to an incorrect‐
ly selected switch-off delay
31/85