Bosch Rexroth IndraControl S20 Manual page 26

Hide thumbs Also See for Rexroth IndraControl S20:
Table of Contents

Advertisement

24/85
Bosch Rexroth AG
Mounting, demounting and electric installation
12-pin DIP switch: Address
Setting address
IndraControl S20 Module With Safe Digital Outputs S20-SSDO-8/3
S1
DIP switch to set the SDID and SNN
Fig. 5-1:
DIP switch
Set the TUNID (SDID + SNN) for the CSos device.
The SDID addresses from 1 to 127 (1
The SNN addresses from 1 to 31 (1
The TUNID is shown as follows: TUNID =SDID*1000000000000
+ (600000000
+ SNN)
hex
SNN
Address switch
4
3
2
1
MSB
SNN
1
to 1F
hex
hex
MSB
The MSB (most significant bit) has the highest significance.
LSB
The LSB (least significant bit) has the lowest significance.
Tab. 5-1:
Switch position at CSos
Example:
Calculating the TUNID using the DIP switch position
SDID: 23 = 17
⇒ DIP switches 4, 2, 1 and 0 to "on"
hex
SNN: 1 = 1
⇒ DIP switch 0 to "on"
hex
Resulting TUNID: 00000017000600000001
1.
Remove the labeling field.
2.
Set the address.
3.
Attach the labeling field again to the module.
DOK-CONTRL-S20*SSDO*8*-AP02-EN-P
TUNID
S 1
4
2
0
3
1
S NN
to 7F
) are permitted.
hex
hex
to 1F
) are permitted.
hex
hex
SDID
0
6
5
4
LSB
MSB
SNN
SDID
1
to 7F
hex
hex
hex
off
on
5
3
1
6
4
2
0
S DID
hex
3
2
1
0
LSB
SDID