58/85
Bosch Rexroth AG
Technical data and ordering data
11.2.7
Supply voltage U
11.2.8
Safe digital outputs
IndraControl S20 Module With Safe Digital Outputs S20-SSDO-8/3
(actuators)
O
Nominal voltage
Ripple factor
Valid voltage range
Current consumption
Valid interruption period
Overvoltage protection
Reverse voltage protection
Undervoltage detection
Diagnostic displays
External protection
Tab. 11-8:
Supply voltage U
WARNING
Use voltage supplies acc. to EN 50178/VDE 0160 (PELV).
DANGER
●
Due to the maximum current carrying capacity of 8 A, protect the volt‐
age supply U
externally with a fuse of 8 A (slow).
I
●
Only use PELV power supply units with at least 4 times the nominal cur‐
rent required for triggering, as thus, only triggering times of less than
300 ms can be ensured.
Number
Supply
Maximum output current per output
(channel)
Maximum output current of all outputs
(total current)
Maximum output current per group (total current)
DOK-CONTRL-S20*SSDO*8*-AP02-EN-P
24 V DC acc. to EN 61131-2 and EN 60204
3.6 V
SS
19.2 V DC to 30.2 V DC (incl. all tolerances and
ripple)
Typ. 25 mA (all outputs set, supplied by U
30.2 V DC, without actuator supply)
10 ms
The output voltage for the safe outputs disrupts
during this period, as the outputs are not internally
buffered.
Yes (in the module)
Yes (in the module)
Yes, at approx. 17 V
Green LED U
, refer to
chapter 3.7 "Local diag‐
O
nostic and status displays" on page 15
Max. 8 A, slow
(actuators)
O
Loss of the safety functions due to the use of
unsuitable voltage supplies.
The module is provided with a parallel re‐
verse polarity protection. This protection is
only temporally limited. To avoid a module
defect, proceed as follows:
4 dual-channel or 8 single-channel (pulse
switching)
From supply voltage U
2 A
1.5 A (acc. to CUL
8 A
6 A (acc. to CUL
US
at
O
O
)
US
)