Device Parameters (Safe Parameterization); Csos Diagnostic Messages - Bosch Rexroth IndraControl S20 Manual

Hide thumbs Also See for Rexroth IndraControl S20:
Table of Contents

Advertisement

DOK-CONTRL-S20*SSDO*8*-AP02-EN-P
IndraControl S20 Module With Safe Digital Outputs S20-SSDO-8/3
13.3

Device parameters (safe parameterization)

SCCRC
13.4

CSos diagnostic messages

Error code
Error cause
Dec
Hex
6144
0x1800
Configuration is owned
by another originator
6145
0x1801
Output is owned by an‐
other originator
6147
0x1803
Electronic Key mis‐
match: Product Code
or Vendor ID
6148
0x1804
Electronic Key mis‐
match: Device Type
6149
0x1805
Electronic Key mis‐
match: Revision
6150
0x1806
Output Connection
Point not found
6151
0x1807
App.Path: Configura‐
tion Class invalid
6152
0x1808
App.Path: Configura‐
tion Assembly Instance
invalid
6153
0x1809
App.Path: Config. As‐
sembly Instance does
not exist
6154
0x180A
SCCRC mismatch in
Type1 SafetyOpen
The device parameters are individual module parameters within the safe pa‐
rameterization, refer to
chapter 6.2 "Parameterizing the safe outputs" on
page
29.
The device parameters are crosschecked with a checksum, the Safety Con‐
figuration CRC (SCCRC).
Description
The module was configured by an‐
other originator
The module was configured by an‐
other originator
The configured device (SDDML
file) does not match the physically
installed module
The configured device (SDDML
file) does not match the physically
installed module
The configured device (SDDML
file) does not match the physically
installed module
The configured device (SDDML
file) does not match the physically
installed module
The configured device (SDDML
file) does not match the physically
installed module
The configured device (SDDML
file) does not match the physically
installed module
The configured device (SDDML
file) does not match the physically
installed module
The SCCRC entered into the user
interface under "Safe Configura‐
tion" does not match the SCCRC
calculated in the "Safe Parameter‐
ization"
Bosch Rexroth AG
CSos parameters and device parameters
Solution
Change SNN or SDID using DIP
switches. The safe originator ID is
deleted upon a new voltage start‐
up.
Change SNN or SDID using DIP
switches. The safe originator ID is
deleted upon a new voltage start‐
up.
Request new SDDML file or install
the correct module
Request new SDDML file or install
the correct module
Request new SDDML file or install
the correct module
Request new SDDML file or install
the correct module
Request new SDDML file or install
the correct module
Request new SDDML file or install
the correct module
Request new SDDML file or install
the correct module
Copy SCCRC from the "Safe Pa‐
rameterization" to the "Safe Con‐
figuration"
67/85