Errors Of The Supply Voltage; Parameterization Errors - Bosch Rexroth IndraControl S20 Manual

Hide thumbs Also See for Rexroth IndraControl S20:
Table of Contents

Advertisement

DOK-CONTRL-S20*SSDO*8*-AP02-EN-P
IndraControl S20 Module With Safe Digital Outputs S20-SSDO-8/3
Code
Error cause
0x8F09
Dark test error at the
displayed output
0x2380
Hardware or cross-
fault errors
0x5010
Hardware error
9.2.3

Errors of the supply voltage

Code
Error cause
0x3411
Undervoltage U
sup‐
O
ply
9.2.4

Parameterization errors

LED
Description, effect
All
Due to the test pulses (short-term switch-
OUT
off), an error was detected at the dis‐
red on
played output. All outputs are thus re‐
tained in the safe state.
All
The displayed output cannot be disabled.
OUT
All outputs are thus retained in the safe
red on
state.
-
Due to the internal self test mechanism, a
hardware error was detected at the out‐
puts. All outputs are thus retained in the
safe state.
Tab. 9-9:
Errors of the safe digital outputs
LED
Description, effect
UI
Undervoltage was detected at the U
flash‐
supply. A diagnostic message is gener‐
ing
ated if U
< 17 V.
O
All outputs of the module are retained in
the safe state.
The U
LED is permanently on again, as
O
soon as no undervoltage is detected.
Tab. 9-10:
Supply voltage error
Parameterization errors cause diagnostic messages of priority 1 in the Dia‐
gState object. These errors cannot be acknowledged: The parameterization
has to be checked and corrected.
To identify the type of parameterization error, go online with IndraWorks on
the control and read out the error.
Bosch Rexroth AG
Errors: Reporting and troubleshooting
Acknowledgement, remedy
Read out channel number via the
DiagStateChannelNo object 0x033.
This diagnostic message can be
acknowledged. The acknowledge‐
ment deletes the message and en‐
ables the outputs.
Multiple acknowledgement can be
required for the error.
Read out channel number via the
DiagStateChannelNo object 0x033.
This diagnostic message can be
acknowledged. The acknowledge‐
ment deletes the message and en‐
ables the outputs.
This diagnostic message can be
acknowledged. The acknowledge‐
ment deletes the diagnostic mes‐
sage.
It can only be restarted after an
error-free power-up self test.
If the power-up self test results in
errors, the module has to be re‐
placed.
Acknowledgement, remedy
Check and correct the supply volt‐
O
age.
Check length and load of the sup‐
ply lines.
This diagnostic message can be
acknowledged. The acknowledge‐
ment deletes the message and en‐
ables the outputs.
49/85

Advertisement

Table of Contents
loading

This manual is also suitable for:

S20-ssdo-8/3R911173192

Table of Contents