Functions

3.19 Integrated manual local control

3.19
Integrated manual local control
Integrated manual local control (ordering option) for the M200D motor starter involves a key-
operated switch and a keypad with four pushbuttons.
Key-operated switch
Figure 3-12
The key-operated switch can be set to three different positions.
Position
Note
The key can be inserted/removed in any position.
84
Key-operated switch
Meaning
Automatic mode
Manual mode
OFF / Reset
Function
The pushbuttons on the keypad have no function. The
LEDs on the "quick stop disable", "RIGHT", and "LEFT"
pushbuttons, however, are active. They are used for
indicating the status (= status of control via the PIO).
Control priority is assumed by a lower-priority control
source (automatic mode) and transferred to the keypad.
When you switch back to "REMOTE", control priority is
always initially passed to the CPU/master.
The motor starter does not execute any control commands
in this position (regardless of the control source). When
"exiting" this switch position (after both automatic and
manual mode), any error/fault that is still present is
acknowledged. This reset is carried out regardless of the
current operating mode.