Motor starter version
Typ. switching times incl. internal signal
processing at 0.85 to 1.1 x U
Mechanical service life of contactor
Electrical service life of contactor
B10 value
Permissible switching frequency
Isolation stability
Rated impulse withstand voltage U
Rated insulation voltage U
Safe isolation between main and control circuits
to IEC 60947-1 Appendix N
Short-circuit protection
Instantaneous overcurrent release
- I
= 2 A
e max
- I
= 9/12 A
e max
Rated short-circuit¬breaking capacity I
with IEC 60947
at 400 V
at 500 V
Short circuit ratings according to UL / CSA
Group installation
Motor disconnect
1) This specification refers exclusively to the mechanical switching element under its reference conditions.
Note
To reverse the direction of rotation, a mechanically-switching reversing contactor is
integrated in reversing starters with electronic switching. The preferred position of this
contactor is "CW rotation". When the direction is changed to "CCW rotation", the reversing
contactor is activated first, followed by the electronic contacts after an 80 ms delay.
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004
- Closing delay
- Opening delay
e
imp
i
at 400 V in accordance
CU
DSte/RSte
50 to 85 ms
40 to 65 ms
30 million
See Electrical service life
of contactor (Page 156)
1000000
See Electrical service life
of contactor (Page 156)
500 V
400 V
26 A
208 A
50 kA
50 kA
65 kA / 480 V /
Any circuit breaker or any
fuse
10 kA / 600 V /
Any circuit breaker or any
fuse
Suitable for Group installation
Suitable as motor disconnect
Technical data
8.2 Motor starters
sDSSte/sRSSte
25 / 105 ms
35 / 35 ms
1)
See Switching frequency
(Page 148)
6 kV
50 kA
20 kA
5 kA / 480 V /
Fuse: 60 A class J
42 kA / 480 V /
Fuse: 45 A class J
145