Byte.Bit
Parameter
8.2
Response to
asymmetry
8.3 to 6
Connector
monitoring
8.7
Free
9.0 to 3
Response when
connector removed
9.4
Group diagnostics
9.5
Response to
CPU/Master STOP
9.6 to 7
Free
10
Lower current limit
11
Upper current limit
12.0
Input 1 level
12.1
Input 2 level
12.2
Input 3 level
123
Input 4 level
12.4
Input 1 signal
12.5
Input 2 signal
12.6
Input 3 signal
12.7
Input 4 signal
13.0 to 3
Input 1 action
13.4 to 7
Input 2 action
14.0 to 3
Input 3 action
14.4 to 7
Input 4 action
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004
Value range/[code]
[0] Warning
[1] Trip
[0]: Deactivated
[1]: Line side
—
[0] Group fault
[1] Group fault only with ON
command
[2] Group warning
[0] Block
[1] Enable
[0] Switch substitute value
[1] Retain last value
—
[6 to 32] 18.75 to 100%
[0] Deactivated
[16 to 128] 50% to 150, 400%
[0] Deactivated
[0] Normally closed
[1] Normally open
[0] Normally closed
[1] Normally open
[0] Normally closed
[1] Normally open
[0] Normally closed
[1] Normally open
[0] Non-retentive
[1] Retentive
[0] Non-retentive
[1] Retentive
[0] Non-retentive
[1] Retentive
[0] Non-retentive
[1] Retentive
[0] No action
[1] Trip without restart
[2] Trip with restart
[3] Trip end position CW
[4] Trip end position CCW
[5] Group warning
[6] Manual mode local
[7] Emergency start
[8] Motor CW
[9] Motor CCW (on RS only)
[11] Quick stop
[12] Trip reset
[13] Cold start
A.2 Data formats and data sets
Increment
Default setting
—
[1] Trip
—
[0] Deactivated
—
—
—
[0] Group fault
[0] Blocked
—
[0] Switch substitute
value
—
—
3.125%
[6] 18.75%
3.125%
[36] 112.5%
—
[1] Normally open
—
[1] Normally open
—
[1] Normally open
—
[1] Normally open
—
[0] Non-retentive
—
[0] Non-retentive
—
[0] Non-retentive
—
[0] Non-retentive
—
[0] No action
—
[0] No action
—
[0] No action
—
[0] No action
Appendix
Relevant
for
All
All
—
All
All
All
—
All
All
All
All
All
All
All
All
All
All
All
All
All
All
177