Configuring/assigning parameters
5.4 Assigning parameters
5.4.2

Parameter overview

The table below provides an overview of all the M200D parameters and indicates which
mechanism can be used to adjust each of the parameters.
Device parameter
Rated operational
current
Load type
Protection against
voltage failure
Response to switching
element supply voltage
cut-off
Response to
CPU/Master STOP
Group diagnostics
Wait for "Parameter"
startup data set
Lock-out time
Startup time (x 0.25 s)
Run-down time
Startup mode
Run-down type
Starting voltage
Stopping voltage
Current limit value
(x 3.125%)
116
Default setting
In the motor
0.15 A to 2.0 A
starter:
1.5 A to 9.0 A (only with soft starters
Maximum
in "direct" startup mode)
value
1.5 A to 12.0 A
In Motor
Increment: 10 mA
Starter ES:
Minimum value
3-phase
3-phase/1-phase
Yes
Yes/no
Group fault
Group fault
Group fault only after ON command
Group warning
Switch substitute
Switch substitute value/
value
hold last value
Block
Block/enable
No
Yes/no
(can be set using the parameter bit
during configuration)
0
0 to 60 s
Increment: 1 s
5 s
0 to 30 s
Increment: 0.25 s
0
0 to 30 s
Increment: 0.25 s
Direct
Direct
Voltage ramp
Current limit
Voltage ramp + current limit
Run-down without
Run-down without load
load
Voltage ramp
40%
20% to 100%
Increment: 5%
40%
20% to 90%
Increment: 5%
125% to 600%
600% (I
≤ 9 A)
e
Increment: 3.125%
450% (I
> 9 A)
e
Setting range
Manual, 08/2014, A5E02548958A/RS-AA/004
Ext. PI
DS 203
Motor
Starter
ES
M200D AS-Interface Standard