Functions
3.7 System monitoring
Input n action
Motor CW
Motor CCW
(RSte/sRSSte only)
Quick stop
Trip reset
Cold run
NO
Normally open contact
NC
Normally closed contact
Ret.
Retentive
N-ret.
Non-retentive
Activation and deactivation of the input action follows the status of the input signal (= jog) ^
56
Level
Signal
NO/-
n-ret./ret.
NO/-
n-ret./ret.
NO/NC
n-ret./ret.
NO/-
n-ret./-
NO/-
n-ret./-
Mode
Manual local
The motor starter must be in "manual local"
mode for these actions.
Manual local
The device parameters of the braking operation
are evaluated.
"Motor CW": Switches the motor and the brake
output on and off (clockwise) at the same time.
"Motor CCW": Switches the motor and the brake
output on and off (counter-clockwise) at the
same time.
Only allowed as an NO contact.
The input action is triggered while the active
ret.:
level of the input signal is pending.
Input trigger is canceled using the input action
"Quick stop" or group fault.
All
The motor and brake output are switched off
without a group fault.
"Quick stop" has priority over "Motor CW" and
"Motor CCW".
The input action responds to the active edge of
ret.:
the input signal. This makes deactivation with a
pending active input signal possible.
The input trigger is canceled by removing the control
commands "Motor CW" and "Motor CCW"
All
"Trip reset" is triggered once.
Only possible as NO contact.
All
Enables switch-on without main power supply. If
the main power supply is present (current is
flowing), however, an internal trip command is
generated.
Description
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004