3.10

Logbook

Description
The logbook contains a chronological list of triggering operations, device errors, and events,
which are assigned a time stamp and can be used to create a log. The log is stored internally
so that the causes can be evaluated at a later stage.
Note
You require Motor Starter ES for this function.
Logbooks
There are 3 different logbooks that can be read out using Motor Starter ES:
● Logbook - Triggering operations
● Logbook - Events
● Logbook - Device errors
The current value for "Operating hours - Device" is entered as the time stamp.
The last 21 entries are stored in the logbooks.
The logbook has been designed as a circular buffer. After 21 entries, the oldest entry is
overwritten.
Logbook - Triggering operations
The "Logbook - Triggering operations" contains all the group faults. The fault texts of the
actual fault causes are entered, e.g. "Switching element overload".
Please note that the "Logbook - Triggering operations" is deleted with the command "Delete
logbook - Triggering operations".
Logbook - Events
The "Logbook - Events" contains all the warnings as well as certain actions.
Please observe the following:
● "Incoming" and "outgoing" events are entered:
"Incoming" means: The event is occurring.
"Outgoing" means: The event is acknowledged.
The entries are differentiated in the data set by means of their sign:
(+: Incoming, –: Outgoing).
● The "Logbook - Events" is deleted with the command "Delete logbook - Events".
Logbook - Device errors
The "Logbook - Device errors" records all the device errors that occur.
Please note that the "Logbook - Device errors" cannot be deleted.