Restoring factory settings
You can restore the factory settings as follows:
● With the "Factory setting" command (using data set 93 or Motor Starter ES).
This is only possible if "Manual" mode is set and the switching elements are deactivated.
● With the disconnecting means
Turn the knob of the disconnecting means within the specified time window of 2 to 4
seconds to the positions ON and OFF as shown in the time diagram below, and monitor
the LEDs on the motor starter as you do so.
Figure 3-10
Factory settings
The introduction sequence prevents accidental resetting to the factory settings.
The factory setting operation is introduced with the beginning of the start sequence. The
LEDs behave as follows here:
● SF off
● STAT off
● DEVICE flashes red
When the factory settings are restored, the LEDs behave as follows for 5 seconds:
● SF off
● STAT off
● DEVICE flickers red
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004
Functions
3.14 Factory settings