Functions
3.6 Motor protection
Trip class
The trip class (CLASS) specifies the maximum time within which a protective device must
trip from a cold state at 7.2x the current setting (motor protection to IEC 60947). The tripping
characteristics represent this time to disengagement as a function of the tripping current.
Figure 3-4
Note
The setting options for the trip classes are dependent on the motor starter and the current
range.
The following trip classes can be parameterized:
● CLASS 5 (10a)
● CLASS 10
● CLASS 15
● CLASS 20
● CLASS OFF (deactivates the thermal motor model)
40
Tripping characteristics
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004