DS error
_H
_L
_Highbyte
_Lowbyte
80
B0
H
H
80
B1
H
H
80
B6
H
H
80
B8
H
H
80
C2
H
H
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004
Error message
From technology function (= access)
Unknown data set
n umber
Incorrect data set length when
writing
Device has rejected data transfer
Invalid parameter
From device (= resource)
Temporary lack of resources in the
device
A.1 Acyclic data transfer via CTT2
Possible causes
DS no. not supported by
•
device
DS length ≠ specified DS
•
length
Due to incorrect mode
•
Data set is read-only
•
Parameter change not
•
permissible in current
device/system operating
mode
Incorrect/invalid parameter
•
values were received
No free receive buffer
•
The data set is currently
•
being updated
The data set job is
•
currently being processed
on a different interface
Appendix
Remedial measures
None, since the
•
device does not
recognize this data
set no.
Change DS length to
•
match specified
length and send DS
again
Check whether
The correct mode is
•
set on the device for
the data sent
A data set that can
•
only be read is to be
written
A parameter has been
•
changed even though
it may only be
changed in a
particular operating
mode
Change the
•
parameter value to a
valid one and resend.
Attempt
•
communication again!
167