Siemens SIRIUS M200D Manual page 35

Industrial controls load feeders and motor starters
Hide thumbs Also See for SIRIUS M200D:
Table of Contents

Advertisement

Stopping voltage
The stopping voltage is the final value of the voltage ramp for soft run-down. The voltage
ramp is run to the stopping voltage and then switched off.
Current limit value
With the startup modes "Current limiting" and "Voltage ramp + current limiting", the motor
current is limited to a maximum value during starting.
Note
At a rated operating current ≥ 9 A, the motor starter automatically reduces the current limit
value to 550%.
Settings
Starting time
Run-down time
Startup mode
Run-down type
Starting voltage
Stopping voltage
Current limit value
Messages and actions
Starting active
Run-down active
No supply voltage
Current limiting active
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004
Device parameter
Message
The motor is switched on depending on the "Startup mode" parameter.
The motor is switched on depending on the "Run-down mode"
parameter.
ON command generates faults.
Motor starting current is limited.
Default setting
5 s
0
direct
Run-down without load
40%
40%
600% (I
≤ 9 A)
e
550% (I
> 9 A)
e
Action
3.5 Motor control
Setting range
0 to 30 seconds
Increment: 0.25 s
0 to 30 s
Increment: 0.25 s
direct
Voltage ramp
Current limit
Voltage ramp + current limit
Run-down without load
Voltage ramp
20% to 100%
Increment: 5%
20% to 90%
Increment: 5%
I
≤ 9 A: 125% to 600%
e
I
> 9 A: 125% to 550%
e
Increment: 3.125%
Functions
35

Advertisement

Table of Contents
loading

Table of Contents