DEVICE LED (possible colors: Red/green/yellow/OFF)
Status
Off
Green
Flashing green
Yellow
Flashing yellow
Red
Flashing red
Flickering red
Depends on the parameter assignment
1)
AS-i/fault LED (possible colors: Red/green/OFF)
Status
Off
Green
Flashing red/yellow
Flashing red/green
Flashing red
Red
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004
Meaning
Device not ready
Device ready
Device not starting up
Internal tripping
Group warning
Device defective
Self-test
Self-test
Factory settings
Meaning
Device not ready
Device ready
Slave address = 0
I/O fault
Serious I/O fault
No data exchange
7.1 Diagnostics with LEDs
Cause
System error:
No supply voltage for electronics or power supply
is < 18 V
No startup parameters received
Group warning due to:
Current not flowing despite ON command
(residual current detected)
Thermal motor model overload
Temperature sensor overload
Asymmetry
Current limit violation
1)
Group warning via input action
Invalid parameter value
Connector monitoring
Circuit breaker tripped/open
No switching element supply voltage
A device defect was detected during the self-test.
Motor current flowing
No current flow
Cause
No supply voltage for electronics
Hardware fault in AS-i slave
Communication active, normal operation
S1 bit set and group diagnostics = enabled
Hardware fault in AS-i slave
Master in stop mode
Slave not entered in LPS
Slave has wrong IO/ID code
Slave in reset status
Diagnostics
1)
1)
1)
1)
1)
1)
133