Mounting/Connecting
4.2 Connecting
The following maximum current-carrying capacities apply for PVC power cables when
installed, for example, in the cable duct (depending on the ambient temperature):
Cross-section
1.5 mm
2.5 mm
4.0 mm
6.0 mm
Note
Unused connections
Seal unused connections by means of the sealing caps enclosed since this is the only way to
ensure degree of protection IP65.
The sealing caps are also available as accessories:
Item
Sealing cap M12
4.2.3

Prefabricating power cables

To prefabricate power cables, you require the following:
● A crimping tool for attaching the sockets and pins on the individual wires
● For infeed on motor starters
Assignment of X1: see section Power terminal (Page 100):
– A flexible Cu cable with 4 x 2.5 mm
– Han Q4/2 socket power connector
Item
Contact socket 2.5 mm
Contact socket 4 mm
Contact socket 6 mm
Crimping tool 4 / 6 mm²
98
T
= 30 °C
U
14 A
2
19 A
2
26 A
2
33 A
2
(for motor starters with 230 V AC brake output: 5-core cable; 3 wire + N + PE)
, for Han Q4/2 sockets
2
, for Han Q4/2 sockets
2
, for Han Q4/2 sockets
2
T
= 40 °C
T
= 45 °C
U
U
12.2 A
11.1 A
16.5 A
15.0 A
22.6 A
20.5 A
28.7 A
26.1 A
/ 4 mm
/ 6 mm
2
2
T
= 50 °C
T
U
9.9 A
8.5 A
13.5 A
11.6 A
18.5 A
15.9 A
23.4 A
18.2 A
Quantity
Order no.
10 pieces
3RK1901-1KA00
(3 wire + PE)
2
Quantity
Order no.
5
3RK1911-2BE50
5
3RK1911-2BE10
5
3RK1911-2BE30
1
3RK1902-0CW00
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004