3.9 Communication
3.9.5

Messages output

Ready (automatic)
Group fault
Group warning
Process image error
Bus error
CPU/Master STOP
Trip reset executed
Trip reset not possible
Automatic mode
Manual mode local PC
Manual mode local input controls
Connection abort in manual mode
Parameter assignment active
Invalid parameter value
Parameters cannot be changed in ON state
Parameters disabled CPU/master active
No external startup parameters received
Message bits that can be deleted with trip reset
1)
74
Message
General messages
Fieldbus interface
Acknowledgment
Mode monitoring
Parameter assignment
1)
1)
Meaning
Device can be controlled via BUS
Automatic mode
No fault
At least one fault is set.
At least one warning is present.
The process image of the outputs contains an
illegal bit combination, e.g. motor CW and motor
CCW set simultaneously.
AS-i interface threshold monitoring expired.
PLC program is no longer processed.
Trip reset accepted; that is, error/fault has been
acknowledged.
Fault could not be acknowledged since the cause
of the tripping is still pending.
Automatic (PLC controls)
Manual mode via local device interface
Hand-held device, PC
Control signals at the inputs
During manual mode, the relevant
communication connection was interrupted for
more than 5 seconds.
Yes/no
Parameter not correct
Attempt to change parameters while motor is is
running not permissible.
Motor starter ignores parameters from the PLC
but informs the PLC that the parameters are in
order.
No new parameters have been received from the
PLC after Power ON or restart of the motor
starter.