Blocking protection principle in run-up phase:
The figure below shows the principle of blocking protection during the run-up phase; that is,
the interaction between the blocking current and blocking time:
Figure 3-6
Blocking protection principle after run-up phase
Following the run-up phase, blocking protection behaves as follows during uninterrupted
duty:
● The blocking time is reduced to 1 s regardless of the parameterized value.
● The blocking current is limited to a maximum of 400%.
With a parameterized blocking current < 400%, the parameter value is valid.
● When the blocking protection responds, the motor starter itself generates a trip command.
● The messages "Tripping due to motor blocking" and "Group fault" are generated.
● The maximum pointer "Number of switch element overload trips" is incremented by 1.
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004
Blocking protection principle
Functions
3.7 System monitoring