Input n action
No action
Trip without restart
Trip with restart (auto
reset)
Trip end position CW
Trip end position CCW
(RSte/sRSSte only)
Group warning
Manual mode local
Emergency start
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004
Level
Signal
NO/NC
n-ret./ret.
NO/NC
n-ret./-
NO/NC
n-ret./-
NO/NC
n-ret./-
NO/NC
n-ret./-
NO/NC
n-ret./ret.
NO/NC
n-ret./-
NO/-
n-ret./-
Mode
All
All
Causes the motor and brake to trip.
Must be acknowledged once the cause of
tripping has been rectified (initial status).
All
Causes the motor and brake to trip.
Acknowledged automatically once the cause of
tripping has been rectified (initial status).
All
The motor and the brake output are tripped
regardless of the direction of rotation.
All
The brake output can be switched on again once
the "Brake" and "Motor CW/CCW" control
commands have been canceled.
Trip end position CW: The motor can only be
switched on again with the opposite command
("Motor CCW").
Trip end position CCW: The motor can only be
switched on again with the opposite command
("Motor CW").
All
The "Group warning" message is set.
The motor starter and the brake output are not
tripped.
The input action responds to the active edge of
ret.:
the input signal. This makes deactivation with a
pending active input signal possible.
Action is deactivated with trip reset.
All
Control is only possible via "Input n action":
"Motor CW" and "Motor CCW" (see below)
possible.
Control is not possible over the fieldbus
("Automatic" mode).
"Automatic" mode can only be reinstated if
manual mode local is canceled and "Input n
action": "Motor CW" or "Motor CCW" is not
active.
All
Switches on the motor when an ON switching
command is issued in spite of the fact that an
internal trip command is present.
Switches on the brake output too if an ON
switching command is present for this.
Self-protection of the motor starter remains
active and prevents the device from being
destroyed.
Only allowed as an NO contact.
Functions