Configuring/assigning parameters

5.5 Process data and process image

5.5
Process data and process image
5.5.1

Process image

Definition of process image
The process image is a component of the AS-i master system memory.
At the start of the cyclic program, the signal states of the inputs are transferred to the
process image of inputs.
At the end of the cyclic program, the process image of the output is transferred to the slave
as a signal state.
Input process image (PII)
The table below contains process data and a process image of inputs DI 0 to DI 3:
Slave 2
The PII assignment may change depending on the ID1 code.
Process image for ID1 = 7:
Byte/bit
DI 0
DI 1
DI 2
DI 3
Process image for ID1 = 6:
Byte/bit
DI 0
DI 1
DI 2
DI 3
120
Process image
Ready (automatic)
Motor on
Input 1
(input action: quick stop)
Input 2
(no action)
Process image
Ready (automatic)
Automatic
Input 1
(input action: quick stop)
Input 2
(no action)
Signal: 1 = HIGH, 0 = LOW
0: Starter not ready for host/PLC
1: Starter ready to be operated via host
0: OFF
1: ON (CW/CCW)
0: Not active
1: Active
0: Not active
1: Active
Signal: 1 = HIGH, 0 = LOW
0: Starter not ready for host/PLC
1: Starter ready to be operated via host
0: Starter in "Manual" mode
1: Starter in "Automatic" mode
0: Not active
1: Active
0: Not active
1: Active
M200D AS-Interface Standard