Integrated Manual Local Control - Siemens SIRIUS M200D Manual

Industrial controls, load feeders and motor starters, profibus / profinet
Hide thumbs Also See for SIRIUS M200D:
Table of Contents

Advertisement

Functions

3.20 Integrated manual local control

3.20
Integrated manual local control
Integrated manual local control (ordering option) for the M200D motor starter involves a key-
operated switch and a keypad with four pushbuttons.
Key-operated switch
Figure 3-12
The key-operated switch can be set to three different positions.
Position
Note
The key can be inserted/removed in any position.
82
Key-operated switch
Meaning
Automatic mode
Manual mode
OFF / Reset
Function
The pushbuttons on the keypad have no function. The
LEDs on the "quick stop disable", "RIGHT", and "LEFT"
pushbuttons, however, are active. They are used for
indicating the status (= status of control via the PIO).
Control priority is assumed by a lower-priority control
source (automatic mode) and transferred to the keypad.
When you switch back to "Automatic mode", control priority
is always initially passed to the CPU/master.
When "exiting" this switch position (both after automatic
and after manual mode), any pending fault is
acknowledged. This reset is carried out regardless of the
current operating mode. The motor starter does not
execute any control commands in this position (regardless
of the control source).
Manual, 08/2014, A5E01577426A/RS-AA/004
M200D PROFIBUS/PROFINET

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents