5.2.2

Parameter overview

More information on the individual parameters can be found in Chapter Functions (Page 25).
The table below provides an overview of all parameters of the
M200D PROFIBUS/PROFINET motor starter.
Device parameter
Rated operating
current
Load type
Protection against
voltage failure
Response to no
switching element
supply voltage
Response to
CPU/master STOP
Substitute value
Group diagnostics
Lock-out time
Starting time (x 0.25 s)
Run-down time
Startup mode
Run-down type
Starting voltage
Stopping voltage
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
Default setting
Basic functions / parameters (Page 27)
In the motor starter:
maximum value
In GSD/Motor Starter ES:
minimum value
3-phase
Yes
Group fault
Fieldbus interface (Page 31)
Switch substitute value
0
block
Motor control (Page 33)
0
5 s
0
direct
Run-down without load
40 %
40 %
Configuration / parameterization
Setting range
0.15 A to 2.0 A
1.5 A to 9.0 A
1)
1.5 A to 12.0 A
Increment: 10 mA
3-phase
1-phase
Yes
No
Group fault
Group fault only after ON command
Group warning
Switch substitute value
Retain last value
8 bits (0 or 1)
block
enable
0 to 60 s increment: 1 s
0 to 30 s increment: 0.25 s
0 to 30 s increment: 0.25 s
direct
Voltage ramp
Current limiting
Voltage ramp + current limiting
Run-down without load
Voltage ramp
20 % to 100 % increment: 5 %
20 % to 90 % increment: 5 %
5.2 Parameterize
127