Mitsubishi Electric MELSERVO-J5 User Manual page 306

Ac servo system
Hide thumbs Also See for MELSERVO-J5:
Table of Contents

Advertisement

• ABS transfer mode finish-time time-out check
If ABSM is not turned off within 5 s after the last ABS transmission data ready (19th signal for absolute position data
transmission) is turned on, this will be treated as a transmission error and [AL. 0E5] occurs.
ABSM (ABS transfer mode)
ABSR (ABS request)
ABST (ABS transmission data ready)
[AL. 0E5 ABS time-out warning]
• ABSM-off check during the ABS transfer
If the ABS transfer mode is turned on, and after the transfer starts, if the ABSM is turned off before the 19th ABS transmission
data ready, this will be treated as a transmission error and [AL. 0E5] occurs.
ABSM (ABS transfer mode)
ABSR (ABS request)
ABST (ABS transmission data ready)
[AL. 0E5 ABS time-out warning]
7 ABSOLUTE POSITION DETECTION SYSTEM