MR-J5W_-_G_
Rated sensitivity current ≥ 10 • {Ig1 + Ign + Iga + K • (Ig2 (A-axis) + Igm (A-axis) + Ig2 (B-axis) + Igm (B-axis) + Ig2 (C-axis) +
Igm (C-axis))} [mA] . . . (6.2)
Cable
Noise filter
NV
Servo
amplifier
Iga
Ig1
Ign
Earth-leakage current breaker
Type
Models provided with harmonic and surge reduction
techniques
General models
Ig1: Leakage current on the electric channel from the earth-leakage current breaker to the input terminals of the servo
amplifier
Page 250 Example of leakage current (Ig1, Ig2) per km of CV cable run in metal conduit
Ig2: Leakage current on the electric channel from the output terminals of the servo amplifier to the servo motor
Page 250 Example of leakage current (Ig1, Ig2) per km of CV cable run in metal conduit
Ign: Leakage current when a filter is connected to the input side (4.4 mA per one FR-BIF(-H))
Iga: Servo amplifier leakage current
Page 250 Servo amplifier leakage current example (Iga)
Igm: Servo motor leakage current
Page 250 Servo motor leakage current example (Igm)
Cable
M
A-axis
Ig2
Igm
Cable
M
B-axis
Igm
Ig2
Cable
M
C-axis
Ig2
Igm
Mitsubishi Electric products
NV-SP
NV-SW
NV-CP
NV-CW
NV-HW
BV-C1
NFB
NV-L
K
1
3
6 OPTIONS AND PERIPHERAL EQUIPMENT
6.15 Earth-leakage current breaker
6
249