7.2.3

Connection example

Figure 7-3
7.2.4
Meaning of the LED
7.2.4.1
Meaning of the LED on the Sensor Module Cabinet-Mounted SMC10
Table 7- 9
Meaning of the LEDs on the Sensor Module Cabinet-Mounted SMC10
LED
Color
RDY
-
Off
READY
Green
Continuous
light
Orange
Continuous
light
Red
Continuous
light
Green/
Flashing
red
light 0.5 Hz
Flashing
light 2 Hz
Green/
Flashing
orange
light
or
Red/
orange
Parameters for activating the identification of components via LED are 1.p9210 and 1.p9211 (see DCM List Manual)
1)
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
Connecting the encoder via a Sensor Module Cabinet-Mounted (SMC)
Status
The electronics power supply is missing or outside the
permissible tolerance range.
The component is ready for operation. Cyclic DRIVE-CLiQ
communication is taking place.
DRIVE-CLiQ communication is being established.
This component has at least one fault.
Note:
The LED is activated irrespective of whether the
corresponding messages have been reconfigured.
Firmware is being downloaded.
Firmware download is complete. The system waits for
POWER ON.
Component recognition via LED is activated
Note:
Both options depend on the LED status when component
recognition is activated.
7.2 SMC10 Sensor Module Cabinet-Mounted
Description, cause
.
1)
Additional system components
Remedy
Remove and
acknowledge the fault.
Carry out a
POWER ON.
201