Descriptions of functions
10.4 Communication via PROFIBUS DP
10.4.3.2

PROFIBUS interface in operation

Generic station description file
A generic station description file clearly and completely defines the properties of a
PROFIBUS slave.
The GSD files can be found:
● On the Internet. For the link, see "Preface (Page 3)"
● On the memory card in the directory \\SIEMENS\SINAMICS\DATA\CFG\.
– Universal module
– Axis separator
– Standard telegram1, PZD-2/2
– Standard telegram20, PZD-2/6
– SIEMENS telegram 220, PZD-10/10
– SIEMENS telegram 352, PZD-6/6
– Free telegram, PZD-4/4
– Free telegram, PZD-8/8
– Free telegram, PZD-16/16
– Free telegram, PZD-32/32
– Free telegram, PZD-64/64
– Slave-to-slave, PZD-1
– Slave-to-slave, PZD-2
– Slave-to-slave, PZD-4
– Slave-to-slave, PZD-8
The SINAMICS S DXB GSD file contains among other things standard telegrams, free
telegrams and slave-to-slave telegrams for configuring direct data exchange. With the aid of
these telegram parts and an axis separator, a telegram for the drive unit must be composed
for each drive object.
Processing a GSD file in HW Config is covered in the SIMATIC documentation. Suppliers of
PROFIBUS components can provide their own bus configuration tool. The description of the
respective bus configuration tool is described in the relevant documentation.
Note for commissioning for VIK-NAMUR
To be able to operate a SINAMICS drive as a VIK-NAMUR drive, standard telegram 20 must
be set and the VIK-NAMUR identification number activated via p2042 =1.