Connecting

6.6 Line reactors

6.6
Line reactors
The line impedance, with line reactors factored in, should be between 4% and 10% of the
short-circuit voltage.
Line inductances always need to be provided in the infeed in order to limit voltage dips and
ensure that the SINAMICS DCM functions correctly. In the most straightforward situations
this can be done by using a 4% line reactor.
The only situations in which a line reactor is not required are when the converter is supplied
as the only load by means of a separate transformer winding (converter transformer adapted
to the power level).
Where several converters are used on a transformer winding, line reactors must be used
upstream of every converter.
NOTICE
Sequence of the wiring
Semiconductor fuses should be installed in the converter system upstream of the reactor.
The break times are then achieved by the normally used semiconductor fuses
An incorrect arrangement can destroy a thyristor (short-circuit) and rupture a fuse.
Line reactor selection list
Table 6- 4
3-phase line reactors, rated voltage = 400 V AC, uk = 4%
Article number
Rated current Inductance
6RX1800-4DK00
13 A AC
6RX1800-4DK01
25 A AC
6RX1800-4DK02
51 A AC
6RX1800-4DK03
76 A AC
6RX1800-4DK04
106 A AC
6RX1800-4DK05
174 A AC
6RX1800-4DK06
232 A AC
6RX1800-4DK07
332 A AC
6RX1800-4DK08
374 A AC
6RX1800-4DK10
498 A AC
6RX1800-4DK11
706 A AC
6RX1800-4DK12
996 A AC
6RX1800-4DK13
1328 A AC
6RX1800-4DK14
1660 A AC
6RX1800-4DK15
2490 A AC
146
Copper
Total
losses
losses
2.315 mH
22.8 W
33.1 W
1.158 mH
30.8 W
53.2 W
0.579 mH
43.5 W
73.2 W
0.386 mH
64.4 W
118.5 W
0.278 mH
51.3 W
119.3 W
0.169 mH
164.8 W 206.4 W
0.127 mH
197.4 W 256.2 W
0.089 mH
190.7 W 251.1 W
0.079 mH
186.7 W 251.7 W
0.059 mH
277.0 W 357.4 W
0.042 mH
329.4 W 424.8 W
0.030 mH
390.3 W 562.8 W
0.022 mH
339.3 W 554.5 W
0.018 mH
369.3 W 591.9 W
0.012 mH
587.3 W 1038.3 W
SCCR
Weight
2.0 kA (20 ms)
2.9 kg
5.0 kA (20 ms)
4.4 kg
6.5 kA (100 ms) 10.9 kg
9.0 kA (100 ms) 13.8 kg
15 kA (100 ms)
23.9 kg
15 kA (100 ms)
24.0 kg
20 kA (100 ms)
26.8 kg
24 kA (200 ms)
45.8 kg
24 kA (200 ms)
56.8 kg
35 kA (200 ms)
60.0 kg
55 kA (200 ms)
81.6 kg
75 kA (200 ms)
100.1 kg
75 kA (200 ms)
138.8 kg
75 kA (200 ms)
210.7 kg
75 kA (200 ms)
205.6 kg
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
Rated insulation
voltage
600 V
600 V
600 V
600 V
600 V
600 V
600 V
600 V
600 V
600 V
1000 V
1000 V
1000 V
1000 V
1000 V