Commissioning
8.3 Commissioning using the BOP20 operator panel
8.3.2

Commissioning steps

Note:
Parameters with [D] are data-set dependent. Commissioning must be carried out for each
data set.
〈1〉Access authorization
In order to be able to set the access authorization, drive object 1 (DO1) must be activated at
the BOP20, see Chapter "Displays and using the BOP20 (Page 373)".
Access level
(1)p0003 = 1
(1)p0003 = 2
(1)p0003 = 3
〈2〉Adjust the rated device currents
Note
The US rating must be set at p50067 for Base Drives (type 6RA80xx-2xxxx) manufactured in
North America.
The rated armature DC current for the device must be adjusted by setting p50076[0] (in %)
or p50067 if:
Maximum armature current < 0.5 × rated armature DC current for the device
The rated field DC current for the device must be adapted by setting p50076[1] (in %) if:
Maximum field current < 0.5 × rated field DC current for the device
〈3〉Adjust to the actual device supply voltage
p50078[0]
p50078[1]
274
Standard
Advanced
Expert
Rated input voltage for converter armature (in volts)
Rated input voltage for converter field (in volts)
SINAMICS DCM DC Converter